61610 Channel %1 Block %2: No infeed depth programmed
Parameters: %1 = Channel number
%2 = Block number, label
Definitions: Alarm triggered by following cycles: CYCLE76, CYCLE77, CYCLE96.
Remedy: Check parameter MID.
61611 Channel %1 Block %2: No point of intersection found
Parameters: %1 = Channel number
%2 = Block number, label
Definitions: No intersection could be calculated with the contour. Alarm triggered by following cycle: CYCLE95.
Reaction: Alarm display.
Interface signals are set.
NC Start disable in this channel.
Interpreter stop
Remedy: Check contour programming or modify infeed depth.
Program
Continuation:
Clear alarm with the RESET key. Restart part program
61612 Channel %1 block %2: Thread finishing not possible
Parameters: %1 = Channel number
%2 = Block number, label
Definitions: Alarm triggered by following cycles: CYCLE97, CYCLE98.
Remedy: Check the conditions for thread finishing.
61613 Channel %1 block %2: Undercut position incorrectly defined
Parameters: %1 = Channel number
%2 = Block number, label
Definitions: Alarm triggered by following cycles: CYCLE94, CYCLE96.
Reaction: Alarm display.
Interface signals are set.
NC Start disable in this channel.
Interpreter stop
Remedy: Check value in parameter _VARI.
Program
Continuation:
Clear alarm with the RESET key. Restart part program
61701 Channel %1 block %2: Error in finished part contour description
Parameters: %1 = Channel number
%2 = Block number, label
Definitions: Either none of parameters _NP1, _NP2 and _NP3 supplied or error in finished part contour
programming.
Alarm triggered by following cycle: CYCLE950
Remedy: - Check parameters _NP1, _NP2 and _NP3.
- Check finished-part contour programming.
61702 Channel %1 block %2: Error in blank contour description
Parameters: %1 = Channel number
%2 = Block number, label
Definitions: Either none of parameters _NP5, _NP6 and _NP7 supplied or error in blank contour programming.
The alarm is triggered by the following cycles: CYCLE950
Remedy: - Check parameters _NP5, _NP6 and _NP7.
- Check blank contour programming.