To commission the MCP the automation system must be completely electrically
and mechanically connected with respect to NC, PLC and MCP.
The drives must be secured against accidental moving.
8.7.2 Parameterization of the MCP
Fig. 8-17 below shows the interfaces on the rear of the module:
Rotary switch X30/X31
Keyswitch X50
Power supply X10
(see below for details)
PROFIBUS X20
Handwheels X60/X61
Direct keys X70
Handwheel signal type S1
Customer-spec. operating elements X51
...X54
S3 DIP switch
LEDs 1...4
COM board
Termination equipotential bonding conductor
123
SHIELDM24 P24
Power supply X10
Fig. 8-17 Position of interfaces on rear side of machine control panel
For a detailed description of the electrical and mechanical design and of the
machine control panel interfaces, please refer to:
References: /BH/ Operator Components, Manual
Section: Machine control panel MCP 483
After the MCP has been electrically connected, all LEDs on the front side of the
MCP flash until communication is established between MCP and PLC.
Simultaneously pressing the two keys ”Feed stop” and ”Feed enable” (in the
bottom right corner) displays the version number of the current software version
using the LEDs now lighting continuously.
Version number = V ”Number of lit LEDs on the left LED block”
.
”Number of lit LEDs on the center LED block”.
”Number of lit LEDs on the right LED block”
Automation
system
Interfaces
Display of the
software version