8.7 DP slave: MCP 483
8-213
© Siemens AG 2007 All Rights Reserved
SINUMERIK 840Di sl Manual (HBIsl) – 01/2007 Edition
8.7.4 Configuring the DP slave: MCP 483
This section describes the configuration of a DP slave: MCP 483 by way of ex-
ample of the configuration of a SIMATIC S7 project shown in Fig. 8-19.
The configuration comprises the following modules:
S SIMATIC Station 300 with SINUMERIK 810D/840D and PLC 317–2DP
S SINUMERIK MCP with module: standard, handwheel, extended
To configure DP slave: MCP 483 the following steps must be carried out in the
S7 project:
1. Insert DP slave: MCP 1,226.82 cm the configuration
(see Fig. 8-19, Page 8-213: 1)
2. Set the PROFIBUS address.
3. Insert the modules in DP slave: MCP 483 for the functions required.
(see Fig. 8-19, Page 8-213: 2)
4. Set the I/O addresses for the individual slots.
HW Config – [SINUMERIK840D (configuration) –– PROFIBUS MCP]
DefaultProfile:
Station Edit Insert Target System View Tools Window Help
PROFIBUS(1): DP master system(1)
(9) SINUME
I/O
NC/RC
MOTION CONTROL
SINUMERIK MCP
Universal module
standard, handwheel
standard, handwheel, ex
standard
standard, extended
PROFIBUS(1): DP master system(1)
Slot DP ID Order number/designation I address O address Com...
1 55 standard, handwheel, extended 0...7 0...7
2 2IO ––> standard, handwheel, exten 258...261
3 192 ––> standard, handwheel, exten 8...12 8...9
(0) 810D/840D
2
X1
X2
3
PLC 317–2DP 2AJ10
MPI
DP
IM 360
4 S7 FM NCU
1
2
Fig. 8-19 Configuration with DP slave: MCP 483
The following status of the S7 project into which DP–Slave: MCP 483 is to be
inserted is assumed:
You have created the S7 project
You have set up a SIMATIC 300 station with PROFIBUS master–capable
SINUMERIK controller
To insert a DP slave: MCP 483 into the configuration, open the hardware cata-
log with menu item View > Catalog.
Preconditions: S7
project
DP slave: MCP 483
8 PROFIBUS DP Communication