01/2007
8.9 DP slave: SINAMICSS120
8-226
© Siemens AG 2007 All Rights Reserved
SINUMERIK 840Di sl Manual (HBIsl) -- 01/2007 Edition
Message frame structure
The configuration of the PROFIBUS message frame for a DP s lave S120 must
observe the following framework conditions:
S The process data of the axes or drive objects: ”Drives” must be available
before the process data of all other drive objects (Control Unit, infeed, etc.).
Note
Currently, no message frames must be configured for the Control Unit and
infeed of a drive unit. Error acknowledgement and release are performed in the
STARTER by means of free message frame configuration with BICO.
S The s tructure of the process data for the PROFIBUS message frame config-
ured in HW Config (object sequence and message frame type) must be
identical to the structure configured in STARTER.
Version overviewPROFIBUS message frame
Drive object No
.
Object Frame type
Drive_1 31 SIEMENS message frame 102
Drive_2 42 SIEMENS message frame 103
Drive_3 53 SIEMENS message frame 105
Infeed 24 Free message frame configuration with BICO
Control_Unit 15 Free mes sage frame configuration wi th BICO
Drive_Unit_Addr10
Close Help
The drive objects are provided with data from the P ROFIBUS mes sage frame i n the following order:
Preassignment
Overview
1 Message frame 102, P DA--6/10
2 Message frame 103, P DA--6/10
3 Message frame 105, P DA--6/10
Option
Details
Message frame sel ectionObject
General Cycle sync hronizationConfiguration
DP slave properties
Configuring a message frame in HW Config
Configuring a message frame in ST AR TER
Fig. 8-21 Process data structure: HW Config and STARTER
PROFIB
SDPCommun
c
on