The precondition for setting the PROFIBUS address on the control unit is that
no faults or warnings are displayed.
If faults or warnings are displayed (display: E_xxxx), press the ”–” key to switch
from the alarm mode to parameterization mode.
To set the PROFIBUS address, proceed as follows:
1. Setting the PROFIBUS address (parameter P0918)
– Hold down key ”P” longer than 3 seconds.
=> The current value of the parameter P0918 (PROFIBUS address) is
displayed.
– Use keys ”+” and ”–” to set the desired PROFIBUS address.
– Press ”P” again to quit the input mode.
2. Saving the PROFIBUS node address in the FEPROM
– Press the ”+” or ”–” key
=> Parameter P0652 (acceptance into FEPROM) is displayed
– Press ”P” again to call the input mode.
– Use the ”+” key to change the value to 1 (start writing)
and wait until the write process is acknowledged with 0 on the display.
3. Carrying out POWER ON Reset
– Push the ”POWER ON–RESET” button on the front panel of the drive
module.
=> After power–up, the set PROFIBUS address is active.
For detailed information on commissioning of SIMODRIVE 611 universal drives,
refer to:
/FBU/ SIMODRIVE 611 universal Description of Functions
Section: Parameterizing the Module
Parameterization via display and control unit
and
Section: PROFIBUS DP master settings
Commissioning
Requirements
Sequence of
operations
References