Name Color Status Meaning
Activity Orange lit Data exchange
off No data exchange
PROFINET address (S1)
A logical address can be assigned to the I/O module for communication with PROFINET using
a 10-bit DIP switch S1.
Table 11-19 General settings with switch S1
1 2 3 4 5 6 7 8 9 10 Meaning
on on PROFINET functionality
on on on on on on on on DCP mode
The switch positions 9 and 10 guarantee the PROFINET functionality of the module and must
always be switched "on".
DCP mode
In this mode, there is no default device name.
The device name must be set using initialization and remains saved on the I/O module. It is first
deleted when the factory setting is restored, e.g. using STEP 7 (TIA Portal).
Default device names
The switch positions 1 to 8 define the default device name of the I/O module.
There are up to 128 default device names. If these default device names are used, there is no
need for initialization.
Note
The default device names cannot be reconfigured, for example with the TIA Portal "Assign
device name" function.
If you are connecting the I/O module to a SINUMERIK control as a PROFINET component,
make sure that this functionality is supported by the associated control.
Table 11-20 Default device name with switch S1
1 2 3 4 5 6 7 8 9 10 Default device name
on on on on on on on off pp72x48pn127
off on on on on on on off pp72x48pn126
on off on on on on on off pp72x48pn125
off off on on on on on off pp72x48pn124
on on off on on on on off pp72x48pn123
off on off on on on on off pp72x48pn122
on off off on on on on off pp72x48pn121
off off off on on on on off pp72x48pn120
Connectable components
11.2 PP 72/48D PN
NCU 1760