Digital inputs min. max. Nominal
Low-level voltage (U
L
) -3 V 5 V 0 V
Signal delay time T
PHL
0.5 ms 3 ms -
Signal delay time T
PHL
rapid inputs (X222: DI 3.0 to
3.7)
- - 600 μs
Digital outputs
Characteristics
No galvanic isolation.
Protection against: Short-circuit, overtemperature, and loss of ground.
Automatic disconnection in case of undervoltage.
Terminal assignment for the digital outputs:
The following figure shows an example of the terminal assignment for the digital outputs on
connector X111. Connectors X222 and X333 are assigned analogously.
([WSRZHUVXSSO\
9'&VWDELOL]HG
;;;
3LQQXPEHU
'ULYHU
'ULYHU
'ULYHU
5HOD\
33'$31
9
9

'2&20[
:
:
:
:




1 (M)
0
Figure 11-16 Terminal assignment for the digital outputs
NOTICE
Damage to the module
If the outputs are overloaded, the heat can melt the contacts.
Therefore, for a demand factor of 100%, a max. current of I
out
= 0.25 A at X111, X222, X333:
Pin 2, must not be exceeded.
Technical data:
Connectable components
11.3 PP 72/48D PN 2/2A PN
NCU 1760
136 Equipment Manual, 02/2020, A5E45627861B AB