Siemens SINUMERIK ONE NCU 1760 - Page 140

Siemens SINUMERIK ONE NCU 1760
162 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6LJQDOQDPH
%XV
;
,
F
$'8
&,[
&2[
33'$31
$,[
$,[
x 1, 2
ADU Analog Digital Unit
I
c
Constant current
Figure 11-17 PT100 pin assignment
Measurement using a 3-wire connection system
The following pins must be jumpered at connector X3 in order to perform the measurement in
the PT100 using a 3-wire connection system:
Temperature measurement with channel 1:
Short-circuit pin 2 (CI 1) and pin 4 (AI 1-) and connect the jumper at connector X3
Temperature measurement with channel 2:
Short-circuit pin 6 (CI 2) and pin 8 (AI 2-) and connect the jumper at connector X3.
Note
Measuring accuracy
The accuracy of the temperature input becomes poorer: The resistance of the connecting
cable of the jumpered connecting cable falsifies the measurement.
Analog outputs
The module has two analog outputs. These can optionally be assigned parameters as voltage
or current output.
Note
The analog outputs are only enabled following the parameter assignment.
From the switch-on of the I/O module to when it is enabled, the analog outputs do not read 0 V,
but are defined by a voltage pulse at -0.2 V. This value must be taken into consideration when
specifying the setpoint value.
Connectable components
11.3 PP 72/48D PN 2/2A PN
NCU 1760
140 Equipment Manual, 02/2020, A5E45627861B AB