Loading...
No. Description Function Typ
e of
Info
rma
tion
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log ON/OFF
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
information number
Data Unit
General Interrogation
2975 SYNC voltage Usy2 < U>
(P.3503) (SYNC Usy2<<)
Sync. Check OUT O
N
OF
F
ON
OFF
* LED BO
2976 SYNC voltage Usy1
>Umax (P.3504) (SYNC
Usy1>>)
Sync. Check OUT O
N
OF
F
ON
OFF
* LED BO
2977 SYNC voltage Usy1 < U>
(P.3503) (SYNC Usy1<<)
Sync. Check OUT O
N
OF
F
ON
OFF
* LED BO
2978 SYNC Udiff too large
(Usy2>Usy1) (SYNC
Usy2>Usy1)
Sync. Check OUT O
N
OF
F
ON
OFF
* LED BO
2979 SYNC Udiff too large
(Usy2<Usy1) (SYNC
Usy2<Usy1)
Sync. Check OUT O
N
OF
F
ON
OFF
* LED BO
2980 SYNC fdiff too large
(fsy2>fsy1) (SYNC
fsy2>fsy1)
Sync. Check OUT O
N
OF
F
ON
OFF
* LED BO
2981 SYNC fdiff too large
(fsy2<fsy1) (SYNC
fsy2<fsy1)
Sync. Check OUT O
N
OF
F
ON
OFF
* LED BO
2982 SYNC PHIdiff too large
(PHIsy2>PHIsy1) (SYNC
φsy2>φsy1)
Sync. Check OUT O
N
OF
F
ON
OFF
* LED BO
2983 SYNC PHIdiff too large
(PHIsy2<PHIsy1) (SYNC
φsy2<φsy1)
Sync. Check OUT O
N
OF
F
ON
OFF
* LED BO
6854 >Trip circuit superv. 1:
Trip Relay (>TripC1
TripRel)
Trip-
Circ.Superv
SP O
N
OF
F
* * LED BI BO
6855 >Trip circuit superv. 1:
Breaker Relay (>TripC1
Bkr.Rel)
Trip-
Circ.Superv
SP O
N
OF
F
* * LED BI BO
Functions, Settings, Information
E.3 Information List
330 SIPROTEC 4, 7VK61, Manual
C53000-G1176-C159-5, Edition 05.2018

Table of Contents