EasyManua.ls Logo

Siemens SIPROTEC 7SJ531 - Page 56

Siemens SIPROTEC 7SJ531
362 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
-ETHOD OF OPERATION3*
6
#
' #

 $IRECTIONAL OVERCURRENT TIME PROTECTION OPTIONAL
 'ENERAL
3)02/4%# 3*PROVIDES DEPENDENT OF THE OR
DERED MODEL A DIRECTIONAL OVERCURRENT TIME PROTEC
TION 4HUS IT CAN BE USED IN SYSTEMS WHERE THE DI
RECTION OF ENERGY FLOW TO THE FAULT LOCATION IS REQUIRED
AS A FURTHER CRITERION BESIDES THE OVERCURRENT CRITERI
ON IN ORDER TO ACHIEVE SELECTIVITY
&OR PARALLEL LINES OR TRANSFORMERS WHICH ARE FED FROM
ONE SIDE REFER TO &IGURE  A FAULT ON ONE BRANCH
) CAN RESULT IN THE OTHER BRANCH )) BEING DISCON
NECTED UNLESS THE TRIPPING OF THE CIRCUIT BREAKER IN
THE PARALLEL HEALTHY BRANCH IS PREVENTED BY A DIREC
TIONAL MEASURING ELEMENT AT " 4HEREFORE A DIREC
TIONAL OVERCURRENT SCHEME MUST BE INSTALLED AT THE
POINTS INDICATED BY THE DIRECTIONAL ARROW IN &IGURE
 )T MUST BE NOTED THAT THE
FORWARDS DIRECTION OF
THE DIRECTIONAL RELAY IS THE DIRECTION TO THE PROTECTED
OBJECT 4HIS IS NOT NORMALLY IDENTICAL WITH THE DIREC
TION OF THE NORMAL LOAD FLOW AS CAN BE SEEN IN THE FIG
URE
!LSO IN NETWORKS WITH INFEED FROM BOTH SIDES OR IN
RING NETWORKS THE OVERCURRENT TIME PROTECTION MUST
HAVE A DIRECTIONAL CRITERION &IGURE  SHOWS A RING
NETWORK AS A DEVELOPMENT IN THE ACTUAL RING NET
WORK THE TWO INFEEDS SHOWN IN THE FIGURE MERGE INTO
A SINGLE INFEED
T
T
NORMAL LOAD
DIRECTION
!"
)
))
OVERCURRENT TIME PROTECTION
DIRECTIONAL OVERCURRENT TIME PRO
TECTION
&IGURE  /VERCURRENT TIME PROTECTION FOR PAR
ALLEL TRANSFORMERS
OVERCURRENT TIME PROTECTION
DIRECTIONAL OVERCURRENT TIME PROTECTION
T
T
&IGURE  $OUBLE END FED LINE OR RING FEEDER
www . ElectricalPartManuals . com

Related product manuals