-ETHOD OF OPERATION3*
6
#
' #
$IRECTIONAL OVERCURRENT TIME PROTECTION OPTIONAL
'ENERAL
3)02/4%# 3*PROVIDES DEPENDENT OF THE OR
DERED MODEL A DIRECTIONAL OVERCURRENT TIME PROTEC
TION 4HUS IT CAN BE USED IN SYSTEMS WHERE THE DI
RECTION OF ENERGY FLOW TO THE FAULT LOCATION IS REQUIRED
AS A FURTHER CRITERION BESIDES THE OVERCURRENT CRITERI
ON IN ORDER TO ACHIEVE SELECTIVITY
&OR PARALLEL LINES OR TRANSFORMERS WHICH ARE FED FROM
ONE SIDE REFER TO &IGURE A FAULT ON ONE BRANCH
) CAN RESULT IN THE OTHER BRANCH )) BEING DISCON
NECTED UNLESS THE TRIPPING OF THE CIRCUIT BREAKER IN
THE PARALLEL HEALTHY BRANCH IS PREVENTED BY A DIREC
TIONAL MEASURING ELEMENT AT " 4HEREFORE A DIREC
TIONAL OVERCURRENT SCHEME MUST BE INSTALLED AT THE
POINTS INDICATED BY THE DIRECTIONAL ARROW IN &IGURE
)T MUST BE NOTED THAT THE
FORWARDS DIRECTION OF
THE DIRECTIONAL RELAY IS THE DIRECTION TO THE PROTECTED
OBJECT 4HIS IS NOT NORMALLY IDENTICAL WITH THE DIREC
TION OF THE NORMAL LOAD FLOW AS CAN BE SEEN IN THE FIG
URE
!LSO IN NETWORKS WITH INFEED FROM BOTH SIDES OR IN
RING NETWORKS THE OVERCURRENT TIME PROTECTION MUST
HAVE A DIRECTIONAL CRITERION &IGURE SHOWS A RING
NETWORK AS A DEVELOPMENT IN THE ACTUAL RING NET
WORK THE TWO INFEEDS SHOWN IN THE FIGURE MERGE INTO
A SINGLE INFEED
T
T
NORMAL LOAD
DIRECTION
!"
)
))
OVERCURRENT TIME PROTECTION
DIRECTIONAL OVERCURRENT TIME PRO
TECTION
&IGURE /VERCURRENT TIME PROTECTION FOR PAR
ALLEL TRANSFORMERS
OVERCURRENT TIME PROTECTION
DIRECTIONAL OVERCURRENT TIME PROTECTION
T
T
&IGURE $OUBLE END FED LINE OR RING FEEDER
www . ElectricalPartManuals . com