Data in the PROFIBUS-DP messages
7SJ61...7SJ63, 7SJ65, 6MD63 PROFIBUS-DP – Bus mapping
C53000-L1840-B006-02
1-7
Standard
mapping 2-4
The standard mapping 2-4 contains:
Output direction:
• 3 double-point commands
• 5 single-point commands
Input direction:
• 3 double-point indications
• 26 single-point indications
• 8 measured values (integer)
• 2 metered measurands (unsigned long)
PROFIBUS-DP
configuration data
Standard mapping 2-1:
1FH 1FH 1FH 1FH 1FH 1FH 13H 28H
(100 bytes input- and 9 bytes output direction)
Standard mapping 2-2:
1FH 1FH 1FH 28H
(48 bytes input- and 9 bytes output direction)
Standard mapping 2-3:
1FH 1FH 1FH 1FH 1FH 27H
(80 bytes input- and 8 bytes output direction)
Standard mapping 2-4:
1FH 1BH 21H
(28 bytes input- and 2 bytes output direction)
PROFIBUS-DP
master
At the configuration of a PROFIBUS-DP slave of the SIPROTEC devices
in the parameterization system of the PROFIBUS-DP masters are to
select the following modules for the 7SJ61...7SJ63, 7SJ65, 6MD63
standard mappings and to allocate associated addresses in the I/O
addressing range of the PROFIBUS-DP master:
Standard mapping 2-1:
Module Order number Input
address
Output
address
0 Input – 16 Bytes Addr_Ix
1 Input – 16 Bytes Addr_Ix+16
2 Input – 16 Bytes Addr_Ix+32
3 Input – 16 Bytes Addr_Ix+48
4 Input – 16 Bytes Addr_Ix+64
5 Input – 16 Bytes Addr_Ix+80
6 Input – 4 Bytes Addr_Ix+96
7 Output – 9 Bytes Addr_Ox
Standard mapping 2-2:
Module Order number Input
address
Output
address
0 Input – 16 Bytes Addr_Ix
1 Input – 16 Bytes Addr_Ix+16
2 Input – 16 Bytes Addr_Ix+32
3 Output – 9 Bytes Addr_Ox