Loading...
Data in the PROFIBUS-DP messages
7SJ61...7SJ63, 7SJ65, 6MD63 PROFIBUS-DP – Bus mapping
C53000-L1840-B006-02
1-11
1.5.2 Control mode REMOTE
Control mode with control authority is REMOTE, option of unlocked
control with PROFIBUS-DP.
Changing the “Control mode REMOTE“ to UNLOCKED permits one
unlocked control operation via PROFIBUS-DP. After execution of
the command, the “Control mode REMOTE“ in the SIPROTEC
device will automatically be reset to LOCKED.
A programmed test “Switch in position“ for unlocked control
operations will always be executed.
If, after changing the “Control mode REMOTE“ to UNLOCKED, no
command is received via PROFIBUS-DP for a period of 5 minutes,
then the “Control mode REMOTE“ is automatically reset to
LOCKED.
If the “Control mode REMOTE“ was automatically reset to LOCKED
by the SIPROTEC device then this status can be recognized by the
corresponding bit in the PROFIBUS-DP input message. In this case
the status of “Control mode REMOTE“ in output direction has to be
updated by the PROFIBUS-DP master.
References
Standard mapping 2-1: ref. to chap. 2.1.3
Standard mapping 2-2: ref. to chap. 3.1.3
Standard mapping 2-3: ref. to chap. 4.1.3
Standard mapping 2-4: not pre-allocated
1.5.3 Changing the setting group
In order to change the setting group, the value “10“ = ON must be
transmitted for the corresponding pair of bits and afterwards be reset to
“00“ = “quiescent status“ (controlled by an impulse from the PROFIBUS-
DP master).
Switching ON one setting group automatically switches OFF the current
active setting group. Transmission of the value “01“ = OFF is
insignificant for the change of the setting group and is refused by the
device.
A change of the setting group is only possible via PROFIBUS-DP if the
parameter C
HANGE TO ANOTHER SETTING GROUP (parameter address =
302) has the value "Protocol".
References
Standard mapping 2-1: ref. to chap. 2.1.3
Standard mapping 2-2: ref. to chap. 3.1.3
Standard mapping 2-3: not pre-allocated
Standard mapping 2-4: ref. to chap. 5.1.3