Standard mapping 2-1
7SJ61...7SJ63, 7SJ65, 6MD63 PROFIBUS-DP – Bus mapping
C53000-L1840-B006-02
2-7
2.2.1.8 Directional time overcurrent protection
Offset Designation of the
SIPROTEC objects
Comments Internal
object no.
9/0 Phase A forward 1 = Phase A forward 2628
9/1 Phase B forward 1 = Phase B forward 2629
9/2 Phase C forward 1 = Phase C forward 2630
9/3 Phase A reverse 1 = Phase A reverse 2632
9/4 Phase B reverse 1 = Phase B reverse 2633
9/5 Phase C reverse 1 = Phase C reverse 2634
9/6 Ground forward 1 = Ground forward 2635
9/7 Ground reverse 1 = Ground reverse 2636
10/0 67-2 TRIP 1 = 67-2 TRIP 2649
10/1 67/67-TOC OFF 1 = Directional time overcurrent PHASE is switched
OFF
2651
10/2 67N OFF 1 = Directional time overcurrent GROUND is
switched OFF
2656
10/3 67-1 TRIP 1 = 67-1 TRIP 2665
10/4 67-TOC TRIP 1 = 67-TOC TRIP 2675
10/5 67N-2 TRIP 1 = 67N-2 TRIP 2679
10/6 67N-1 TRIP 1 = 67N-1 TRIP 2683
10/7 67N-TOC TRIP 1 = 67N-TOC TRIP 2686
11/0 67 A picked up 1 = Directional time overcurrent Phase A picked up 2692
11/1 67 B picked up 1 = Directional time overcurrent Phase B picked up 2693
11/2 67 C picked up 1 = Directional time overcurrent Phase C picked up 2694
11/3 67N picked up 1 = Directional time overcurrent GROUND picked up 2695
11/4 67/67N TRIP 1 = Directional time overcurrent TRIP 2696
2.2.1.9 Unbalanced load protection
Offset Designation of the
SIPROTEC objects
Comments Internal
object no.
11/5 46 OFF 1 = Unbalanced load protection is switched OFF 5151
11/6 46 TRIP 1 = 46 TRIP 5170
2.2.1.10 Frequency protection
Offset Designation of the
SIPROTEC objects
Comments Internal
object no.
11/7 81 OFF 1 = Frequency protection is switched OFF 5211
12/0 81-1 TRIP 1 = 81-1 TRIP 5236
12/1 81-2 TRIP 1 = 81-1 TRIP 5237