Standard mapping 2-1
7SJ61...7SJ63, 7SJ65, 6MD63 PROFIBUS-DP – Bus mapping
C53000-L1840-B006-02
2-8
Offset Designation of the
SIPROTEC objects
Comments Internal
object no.
12/2 81-3 TRIP 1 = 81-1 TRIP 5238
12/3 81-4 TRIP 1 = 81-1 TRIP 5239
2.2.1.11 Undervoltage and overvoltage protection
Offset Designation of the
SIPROTEC objects
Comments Internal
object no.
12/4 27 OFF 1 = 27 Undervoltage protection is switched OFF 6530
12/5 27-1 TRIP 1 = 27-1 Undervoltage TRIP 6539
12/6 27-2 TRIP 1 = 27-2 Undervoltage TRIP 6540
12/7 59 OFF 1 = 59 Overvoltage protection is switched OFF 6565
13/0 59-1 TRIP 1 = 59 TRIP 6570
2.2.1.12 Sensitive ground fault protection
Offset Designation of the
SIPROTEC objects
Comments Internal
object no.
13/1 50Ns/67Ns OFF 1 = Sensitive ground fault protection is switched
OFF
1211
13/2 64 Pickup 1 = 64 displacement voltage pick up 1215
13/3 64 TRIP 1 = 64 displacement voltage element TRIP 1217
13/4 50Ns-2 TRIP 1 = 50Ns-2 TRIP 1223
13/5 50Ns-1 TRIP 1 = 50Ns-1 TRIP 1226
13/6 51Ns TRIP 1 = 51Ns TRIP 1229
13/7 Sens.Gnd Pickup 1 = Sensitive ground fault pick up 1271
14/0 Sens. Gnd Ph A 1 = Sensitive ground fault picked up in phase A 1272
14/1 Sens. Gnd Ph B 1 = Sensitive ground fault picked up in phase B 1273
14/2 Sens. Gnd Ph C 1 = Sensitive ground fault picked up in phase C 1274
14/3 SensGnd Forward 1 = Sensitive GND fault in forward direction 1276
14/4 SensGnd Reverse 1 = Sensitive GND fault in reverse direction 1277
14/5 SensGnd undef. 1 = Sensitive GND fault direction undefined 1278
2.2.1.13 Circuit breaker failure protection
Offset Designation of the
SIPROTEC objects
Comments Internal
object no.
14/6 50BF OFF 1 = Circuit breaker failure protection is switched
OFF
1451
14/7 50BF TRIP 1 = Circuit breaker failure TRIP 1471