Standard mapping 2-1
7SJ61...7SJ63, 7SJ65, 6MD63 PROFIBUS-DP – Bus mapping
C53000-L1840-B006-02
2-9
2.2.1.14 Thermal overload protection
Offset Designation of the
SIPROTEC objects
Comments Internal
object no.
15/0 49 O/L OFF 1 = Thermal overload protection is switched OFF 1511
15/1 49 O/L I Alarm 1 = 49 Overload current alarm (I alarm) 1515
15/2 49 O/L <Theta> Alarm 1 = 49 Overload alarm! Near thermal TRIP 1516
15/3 49 Windings O/L 1 = 49 Winding overload 1517
15/4 49 Th O/L TRIP 1 = 49 Thermal overload TRIP 1521
15/5 <reserved> –
2.2.1.15 Motor start protection
Offset Designation of the
SIPROTEC objects
Comments Internal
object no.
15/6 >66 emerg. start 1 = Binary input “Emergency start“ is active 4823
15/7 66 OFF 1 = Motor start protection is switched OFF 4824
16/0 66 TRIP 1 = Motor start protection TRIP 4827
2.2.1.16 Startup supervision
Offset Designation of the
SIPROTEC objects
Comments Internal
object no.
16/1 START-SUP OFF 1 = Startup supervision is switched OFF 6811
16/2 START-SUP OFF 1 = Startup supervision TRIP 6821
16/3 Rotor locked 1 = Rotor locked 6822
16/4 START-SUP pu 1 = Startup supervision Pickup 6823
2.2.1.17 Trip coil monitor
Offset Designation of the
SIPROTEC objects
Comments Internal
object no.
16/5 FAIL: Trip cir. 1 = 74TC Failure trip circuit 6865
2.2.1.18 Cold load pickup setup
Offset Designation of the
SIPROTEC objects
Comments Internal
object no.
16/6 CLP OFF 1 = Cold-load-pickup is switched OFF 1994
16/7 CLP BLOCKED 1 = Cold-load-pickup is BLOCKED 1995
17/0 CLP running 1 = Cold-load-pickup is RUNNING 1996
17/1 Dyn set. ACTIVE 1 = Dynamic settings are ACTIVE 1997