EasyManua.ls Logo

Siemens SIPROTEC4 7SJ61 - 3 Standard Mapping 2-2; Message in Output Direction; Double Commands (with Checkback Indication); Single Commands (Without Checkback Indication)

Siemens SIPROTEC4 7SJ61
66 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7SJ61...7SJ63, 7SJ65, 6MD63 PROFIBUS-DP – Bus mapping
C53000-L1840-B006-02
3-1
3 Standard mapping 2-2
Standard mapping 2-2
3
3.1 Message in output direction
3.1.1 Double commands (with checkback indication)
Ref. to chap. 1.6 for additional notes.
Offset Designation of the
SIPROTEC objects
Comments Internal
object no.
0/0 Q0 ON/OFF
OFF
0/1 Q0 ON/OFF
ON
Impulse output,
3 relays (2-pole On, 1-pole Off)
0/2 Q1 ON/OFF
OFF
0/3 Q1 ON/OFF
ON
Impulse output,
2 relays, 1-pole
0/4 Q8 ON/OFF
OFF
0/5 Q8 ON/OFF
ON
Impulse output,
2 relays, 1-pole
0/6 Q2 ON/OFF
OFF
0/7 Q2 ON/OFF
ON
Impulse output,
2 relays, 1-pole
1/0 Q9 ON/OFF
OFF
1/1 Q9 ON/OFF
ON
Impulse output,
2 relays, 1-pole
1/2 Switching device D1 (UsrDC1)
OFF
1/3 Switching device D1 (UsrDC1)
ON
Impulse output,
4 relays (2-pole)
1/4 Switching device D2 (UsrDC2)
OFF
1/5 Switching device D2 (UsrDC2)
ON
Impulse output,
2 relays, 1-pole
3.1.2 Single commands (without checkback indication)
Ref. to chap. 1.5.1 and 1.6 for additional notes.
Offset Designation of the
SIPROTEC objects
Comments Internal
object no.
1/6 Output channel E1 (UsrSC5)
OFF
1/7 Output channel E1 (UsrSC5)
ON
Impulse output,
1 relay, 1-pole
2/0 Output channel E2 (UsrSC6)
OFF
2/1 Output channel E2 (UsrSC6)
ON
Impulse output,
1 relay, 1-pole

Table of Contents

Related product manuals