Standard mapping 2-2
7SJ61...7SJ63, 7SJ65, 6MD63 PROFIBUS-DP – Bus mapping
C53000-L1840-B006-02
3-6
Offset Designation of the
SIPROTEC objects
Comments Internal
object no.
5/4 Alarm Sum Event 1 = Alarm summary event ON 160
5/5 Relay PICKUP 1 = Relay PICKUP (summary alarm) 501
5/6 Relay TRIP 1 = Relay GENERAL TRIP command
(summary alarm)
511
5/7 <reserved> –
3.2.1.6 Automatic recloser status
Offset Designation of the
SIPROTEC objects
Comments Internal
object no.
6/0 >CB Ready 1 = Binary input “circuit breaker ready“ is active 2730
6/1 79 OFF 1 = AR is switched OFF 2781
6/2 79 ON 1 = AR is switched ON 2782
6/3 79 Close 1 = AR close command 2851
6/4 79 Successful 1 = AR successfully completed 2862
6/5 79 Lockout 1 = AR definitive TRIP 2863
6/6 TRIP Gnd Fault 1 = AR TRIP ground fault 2869
6/7 TRIP Ph Fault 1 = AR TRIP phase fault 2870
3.2.1.7 Time overcurrent protection
Offset Designation of the
SIPROTEC objects
Comments Internal
object no.
7/0 50/51 PH OFF 1 = Time overcurrent phase is OFF 1751
7/1 50N/51N OFF 1 = Time overcurrent ground is OFF 1756
7/2 50(N)/51(N) PU 1 = Time overcurrent PICKUP 1761
7/3 50/51 Ph A PU 1 = Time overcurrent phase A picked up 1762
7/4 50/51 Ph B PU 1 = Time overcurrent phase B picked up 1763
7/5 50/51 Ph C PU 1 = Time overcurrent phase C picked up 1764
7/6 50/51N GND PU 1 = Time overcurrent ground picked up 1765
7/7 50(N)/51(N)TRIP 1 = Time overcurrent TRIP 1791
8/0 50-2 TRIP 1 = 50-2 TRIP 1805
8/1 50-1 TRIP 1 = 50-1 TRIP 1815
8/2 51 picked up 1 = 51 picked up 1820
8/3 51 TRIP 1 = 51 TRIP 1825
8/4 50N-2 TRIP 1 = 50N-2 TRIP 1833
8/5 50N-1 TimeOut 1 = 50N-1 TimeOut 1835
8/6 50N-1 TRIP 1 = 50N-1 TRIP 1836
8/7 51N TRIP 1 = 51N TRIP 1839