Standard mapping 2-3
7SJ61...7SJ63, 7SJ65, 6MD63 PROFIBUS-DP – Bus mapping
C53000-L1840-B006-02
4-6
4.2.1.5 Diagnosis
• Ref. to chap. 1.5.5 and 1.5.6 for additional notes regarding "Error with a summary alarm" and "Alarm summary
event".
Offset Designation of the
SIPROTEC objects
Comments Internal
object no.
6/0 Device OK 1 = Update of the device replica in the SIPROTEC
device completed after initial start or restart
51
6/1 <reserved> –
6/2 Settings Calc. 1 = Setting calculation is running 70
6/3 Error Sum Alarm 1 = Error with a summary alarm ON 140
6/4 Alarm Sum Event 1 = Alarm summary event ON 160
6/5 <reserved> –
6/6 <reserved> –
6/7 <reserved> –
4.2.1.6 Measurement supervision
Offset Designation of the
SIPROTEC objects
Comments Internal
object no.
7/0 Fail I Superv. 1 = Failure: General current supervision 161
7/1 Failure <Sum>I 1 = Failure: Current summation 162
7/2 Fail Ph. Seq. 1 = Failure: Phase sequence 171
7/3 MeasSup OFF 1 = Measurement supervision is switched OFF 197
4.2.1.7 Set point alarms
Offset Designation of the
SIPROTEC objects
Comments Internal
object no.
7/4 SP. Op Hours> 1 = Set point operating hours 272
7/5 SP. IA dmd> 1 = Set point phase A dmd> 273
7/6 SP. IB dmd> 1 = Set point phase B dmd> 274
7/7 SP. IC dmd> 1 = Set point phase C dmd> 275
8/0 SP. I1 dmd> 1 = Set point positive sequence I1 dmd> 276
8/1 SP. |Pdmd|> 1 = Set point |Pdmd|> 277
8/2 SP. |Qdmd|> 1 = Set point |Qdmd|> 278
8/3 SP. |Sdmd|> 1 = Set point |Sdmd|> 279
8/4 SP. 37-1 alarm 1 = Set point 37-1 Undercurrent alarm 284
8/5 SP. PF(55)alarm 1 = Set point 55 Power factor alarm 285
8/6 <reserved> –
8/7 <reserved> –