Siemens SIPROTEC4 7SJ61 - Metered Measurands

Siemens SIPROTEC4 7SJ61
66 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Standard mapping 2-3
7SJ61...7SJ63, 7SJ65, 6MD63 PROFIBUS-DP – Bus mapping
C53000-L1840-B006-02
4-9
4.2.3 Metered measurands
Ref. to chap. 1.3.3 for additional notes regarding scaling of metered measurands.
Offset Designation of the
SIPROTEC objects
Comments Scaling
(2
31
-1 of the unsigned long-
value corresponds to ...)
Internal
object no.
52 Wp(puls) = Pulsed Energy Wp (active)
(metering impulses at binary input)
2
31
-1 impulses 888
56 Wq(puls) = Pulsed Energy Wq (reactive)
(metering impulses at binary input)
2
31
-1 impulses 889
60 WpForward=
Wp Forward (metered measurand
derived from measured value)
2
31
- 1 impulses 924
64 WqForward=
Wq Forward (metered measurand
derived from measured value )
2
31
-1 impulses 925
68 WpReverse =
Wp Reverse (metered measurand
derived from measured value)
2
31
-1 impulses 928
72 WqReverse =
Wq Reverse (metered measurand
derived fom measured value)
2
31
-1 impulses 929
76 Op.Hours= Counter of operating hours of the
primary equipment
2
31
-1 hours 1020