Data in the PROFIBUS-DP messages
7SJ61...7SJ63, 7SJ65, 6MD63 PROFIBUS-DP – Bus mapping
C53000-L1840-B006-02
1-6
1.4 Configuration data of the standard mappings 2-1 to 2-4
There are three standard mappings (standard mapping 2-1 to standard
mapping 2-4) available for the SIPROTEC devices 7SJ61...7SJ63,
7SJ65, 6MD63 for parameterization with DIGSI version 4.2 or higher
which differ in the data size of the PROFIBUS-DP messages.
Standard
mapping 2-1
The standard mapping 2-1 contains:
Output direction:
• 7 double-point commands
• 29 single-point commands
Input direction:
• 7 double-point indications
• 146 single-point indications,
• 25 measured values (integer)
• 6 metered measureands (unsigned long)
• Fault locator: Fault location (integer)
• Counter of operating hours (unsigned long)
Standard
mapping 2-2
The standard mapping 2-2 contains:
Output direction:
• 7 double-point commands
• 29 single-point commands
Input direction:
• 7 double-point indications
• 114 single-point indications
• 10 measured values (integer)
• 2 metered measurands (unsigned long)
• Counter of operating hours (unsigned long)
Standard
mapping 2-3
The standard mapping 2-3 contains:
Output direction:
• 8 double-point commands
• 24 single-point commands
Input direction:
• 8 double-point indications
• 64 single-point indications
• 21 measured values (integer)
• 6 metered measurands (unsigned long)
• Counter of operating hours (unsigned long)