7SJ61...7SJ63, 7SJ65, 6MD63 PROFIBUS-DP – Bus mapping
C53000-L1840-B006-02
2-1
2 Standard mapping 2-1
Standard mapping 2-1
2
2.1 Message in output direction
2.1.1 Double commands (with checkback indication)
• Ref. to chap. 1.6 for additional notes.
Offset Designation of the
SIPROTEC objects
Comments Internal
object no.
0/0 Q0 ON/OFF
OFF
0/1 Q0 ON/OFF
ON
Impulse output,
3 relays (2-pole On, 1-pole Off)
–
0/2 Q1 ON/OFF
OFF
0/3 Q1 ON/OFF
ON
Impulse output,
2 relays, 1-pole
–
0/4 Q8 ON/OFF
OFF
0/5 Q8 ON/OFF
ON
Impulse output,
2 relays, 1-pole
–
0/6 Q2 ON/OFF
OFF
0/7 Q2 ON/OFF
ON
Impulse output,
2 relays, 1-pole
–
1/0 Q9 ON/OFF
OFF
1/1 Q9 ON/OFF
ON
Impulse output,
2 relays, 1-pole
–
1/2 Switching device D1 (UsrDC1)
OFF
1/3 Switching device D1 (UsrDC1)
ON
Impulse output,
4 relays (2-pole)
–
1/4 Switching device D2 (UsrDC2)
OFF
1/4 Switching device D2 (UsrDC2)
ON
Impulse output,
2 relays, 1-pole
–
2.1.2 Single commands (without checkback indication)
• Ref. to chap. 1.5.1 and 1.6 for additional notes.
Offset Designation of the
SIPROTEC objects
Comments Internal
object no.
1/6 Output channel E1 (UsrSC5)
OFF
1/7 Output channel E1 (UsrSC5)
ON
Impulse output,
1 relay, 1-pole
–
2/0 Output channel E2 (UsrSC6)
OFF
2/1 Output channel E2 (UsrSC6)
ON
Impulse output,
1 relay, 1-pole
–