Standard mapping 2-1
7SJ61...7SJ63, 7SJ65, 6MD63 PROFIBUS-DP – Bus mapping
C53000-L1840-B006-02
2-2
Offset Designation of the
SIPROTEC objects
Comments
Internal
object no.
2/2 Output channel E3 (UsrSC10)
OFF
2/3 Output channel E3 (UsrSC10)
ON
Continuous output without restauration,
1 relay, 1-pole
2.1.3 Internal commands
Ref. to chap. 1.5.2 and 1.5.3 for additional notes regarding "Control mode REMOTE" and "Changing the setting
group".
Offset Designation of the
SIPROTEC objects
Comments Internal
object no.
2/4 Auto recl. OFF Deactivation of “Autoreclosing“
2/5 Auto recl. ON Activation of “Autoreclosing“
2782
2/6 Protection OFF Deactivation of protection functions
2/7 Protection ON Activation of potection functions
52
3/0 <reserved>
3/1 <reserved>
3/2 Mode REMOTE Control mode REMOTE = LOCKED
3/3 Mode REMOTE Control mode REMOTE = UNLOCKED
3/4 <reserved>
3/5 <reserved>
3/6 <reserved>
3/7 <reserved>
4/0 Setting group A
4/1 Setting group A Activation of setting group A
53
4/2 Setting group B
4/3 Setting group B Activation of setting group B
54
4/4 Setting group C
4/5 Setting group C Activation of setting group C
55
4/6 Setting group D
4/7 Setting group D Activation of setting group D
56
2.1.4 Application logic CFC
Ref. to chap. 1.5.4 and 1.6 for additional notes.
Offset Designation of the
SIPROTEC objects
Comments Internal
object no.
5/0 CFC-Incoming annunciation 1
(UsCfcSpI1) OFF
5/1 CFC-Incoming annunciation 1
(UsCfcSpI1) ON
Tagging ON/OFF, released as CFC input