EasyManua.ls Logo

Siemens SIPROTEC4 7SJ65 - Undervoltage and Overvoltage Protection; Sensitive Ground Fault Protection; Circuit Breaker Failure Protection

Siemens SIPROTEC4 7SJ65
66 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Standard mapping 2-1
7SJ61...7SJ63, 7SJ65, 6MD63 PROFIBUS-DP – Bus mapping
C53000-L1840-B006-02
2-8
Offset Designation of the
SIPROTEC objects
Comments Internal
object no.
12/2 81-3 TRIP 1 = 81-1 TRIP 5238
12/3 81-4 TRIP 1 = 81-1 TRIP 5239
2.2.1.11 Undervoltage and overvoltage protection
Offset Designation of the
SIPROTEC objects
Comments Internal
object no.
12/4 27 OFF 1 = 27 Undervoltage protection is switched OFF 6530
12/5 27-1 TRIP 1 = 27-1 Undervoltage TRIP 6539
12/6 27-2 TRIP 1 = 27-2 Undervoltage TRIP 6540
12/7 59 OFF 1 = 59 Overvoltage protection is switched OFF 6565
13/0 59-1 TRIP 1 = 59 TRIP 6570
2.2.1.12 Sensitive ground fault protection
Offset Designation of the
SIPROTEC objects
Comments Internal
object no.
13/1 50Ns/67Ns OFF 1 = Sensitive ground fault protection is switched
OFF
1211
13/2 64 Pickup 1 = 64 displacement voltage pick up 1215
13/3 64 TRIP 1 = 64 displacement voltage element TRIP 1217
13/4 50Ns-2 TRIP 1 = 50Ns-2 TRIP 1223
13/5 50Ns-1 TRIP 1 = 50Ns-1 TRIP 1226
13/6 51Ns TRIP 1 = 51Ns TRIP 1229
13/7 Sens.Gnd Pickup 1 = Sensitive ground fault pick up 1271
14/0 Sens. Gnd Ph A 1 = Sensitive ground fault picked up in phase A 1272
14/1 Sens. Gnd Ph B 1 = Sensitive ground fault picked up in phase B 1273
14/2 Sens. Gnd Ph C 1 = Sensitive ground fault picked up in phase C 1274
14/3 SensGnd Forward 1 = Sensitive GND fault in forward direction 1276
14/4 SensGnd Reverse 1 = Sensitive GND fault in reverse direction 1277
14/5 SensGnd undef. 1 = Sensitive GND fault direction undefined 1278
2.2.1.13 Circuit breaker failure protection
Offset Designation of the
SIPROTEC objects
Comments Internal
object no.
14/6 50BF OFF 1 = Circuit breaker failure protection is switched
OFF
1451
14/7 50BF TRIP 1 = Circuit breaker failure TRIP 1471

Table of Contents