Standard mapping 2-1
7SJ61...7SJ63, 7SJ65, 6MD63 PROFIBUS-DP – Bus mapping
C53000-L1840-B006-02
2-10
2.2.1.19 Measurement supervision
Offset Designation of the
SIPROTEC objects
Comments Internal
object no.
17/2 Fail I Superv. 1 = Failure: General current supervision 161
17/3 Failure <Sum>I 1 = Failure: Current summation 162
17/4 Fail Ph. Seq. 1 = Failure: Phase sequence 171
17/5 MeasSup OFF 1 = Measurement supervision is switched OFF 197
2.2.1.20 Set point alarms
Offset Designation of the
SIPROTEC objects
Comments Internal
object no.
17/6 SP. Op Hours> 1 = Set point operating hours 272
17/7 SP. IA dmd> 1 = Set point phase A dmd> 273
18/0 SP. IB dmd> 1 = Set point phase B dmd> 274
18/1 SP. IC dmd> 1 = Set point phase C dmd> 275
18/2 SP. I1 dmd> 1 = Set point positive sequence I1 dmd> 276
18/3 SP. |Pdmd|> 1 = Set point |Pdmd|> 277
18/4 SP. |Qdmd|> 1 = Set point |Qdmd|> 278
18/5 SP. |Sdmd|> 1 = Set point |Sdmd|> 279
18/6 SP. 37-1 alarm 1 = Set point 37-1 undercurrent alarm 284
18/7 SP. PF(55)alarm 1 = Set point 55 power factor alarm 285
2.2.1.21 Status annunciations
• Ref. to chap. 1.5.7 for additional notes regarding "Stop data transmission".
Offset Designation of the
SIPROTEC objects
Comments Internal
object no.
19/0 >No Volt 1 = Binary input “No voltage (fuse blown)" is active –
19/1 DataStop 1 = "Stop data transmssion" is active –
19/2 Test mode 1 = Test mode is active –
19/3 Cntrl Auth (device 7SJ63/6MD63)
1
Control authority
(0 = REMOTE, 1 = LOCAL)
–
19/4 ModeLOCAL (device 7SJ63/6MD63)
1
Control mode LOCAL
(0 = LOCKED, 1 = UNLOCKED)
–
19/5 ModeREMOTE Control mode REMOTE
(0 = LOCKED , 1 = UNLOCKED)
–
19/6 Cntrl Auth (device 7SJ61/62)
2
Control authority
(0 = REMOTE, 1 = LOCAL)
–
19/7 ModeLOCAL (device 7SJ61/62)
2
Control mode LOCAL
(0 = LOCKED, 1 = UNLOCKED)
–
1
Not used in the 7SJ61, 7SJ62.
2
Not used in the 7SJ63, 7SJ65, 6MD63.