Standard mapping 2-1
7SJ61...7SJ63, 7SJ65, 6MD63 PROFIBUS-DP – Bus mapping
C53000-L1840-B006-02
2-11
2.2.2 Measured values
Ref. to chap. 1.3.2 for additional notes regarding scaling of measured values.
2.2.2.1 Recorded measured values
Offset Designation of the
SIPROTEC objects
Comments Scaling
(32767 corresponds to ...)
Internal
object no.
20 Ia = Ia 3276.7 A 601
22 Ib = Ib 3276.7 A 602
24 Ic = Ic 3276.7 A 603
26 In = In 3276.7 A 604
28 Va-b = Va-b 32.767 kV 624
30 Vb-c = Vb-c 32.767 kV 625
32 Vc-a = Vc-a 32.767 kV 626
34 VN = VN 32.767 kV 627
36 P = P (active power) 32.767 MW 641
38 Q = Q (reactive power) 32.767 MVAR 642
40 S = S (apparent power) 32.767 MVAR 645
42 Freq = Frequency 327.67 Hz 644
44 INs Real = Resistive ground current in isol.
systems
3276.7 A 701
46 INs Reac = Reactive ground current in isol.
systems
3276.7 A 702
48 PF = Power Factor 3.2767 901
50 I1 = I1 (positive sequence) 3276.7 A 605
52 I2 = I2 (negative sequence) 3276.7 A 606
54 V1 = V1 (positive sequence) 32.767 kV 629
56 V2 = V2 (negative sequence) 32.767 kV 630
58 <Theta> Rotor Temperature of rotor 327.67 % 805
60 <Theta> Stator Temperature of stator 327.67 % 806
62 Td1= Transducer 1 32.767 mA 996
64 Td2= Transducer 2 32.767 mA 997
2.2.2.2 Measured values – mean values
Offset Designation of the
SIPROTEC objects
Comments Scaling
(32767 corresponds to ...)
Internal
object no.
66 I1 dmd = I1 (positive sequence) demand 3276.7 A 833
68 P dmd = Active power demand 32.767 MW 834