Standard mapping 2-2
7SJ61...7SJ63, 7SJ65, 6MD63 PROFIBUS-DP – Bus mapping
C53000-L1840-B006-02
3-2
Offset Designation of the
SIPROTEC objects
Comments
Internal
object no.
2/2 Output channel E3 (UsrSC10)
OFF
2/3 Output channel E3 (UsrSC10)
ON
Continuous output without restauration,
1 relay, 1-pole
–
3.1.3 Internal commands
• Ref. to chap. 1.5.2 and 1.5.3 for additional notes regarding "Control mode REMOTE" and "Changing the setting
group".
Offset Designation of the
SIPROTEC objects
Comments Internal
object no.
2/4 Auto recl. OFF Deactivation of “Autoreclosing“
2/5 Auto recl. ON Activation of “Autoreclosing“
2782
2/6 Protection OFF Deactivation of protection functions
2/7 Protection ON Activation of potection functions
52
3/0 <reserved>
3/1 <reserved>
–
3/2 Mode REMOTE Control mode REMOTE = LOCKED
3/3 Mode REMOTE Control mode REMOTE = UNLOCKED
–
3/4 <reserved>
3/5 <reserved>
–
3/6 <reserved>
3/7 <reserved>
–
4/0 Setting group A
4/1 Setting group A Activation of setting group A
53
4/2 Setting group B
4/3 Setting group B Activation of setting group B
54
4/4 Setting group C
4/5 Setting group C Activation of setting group C
55
4/6 Setting group D
4/7 Setting group D Activation of setting group D
56
3.1.4 Application logic CFC
• Ref. to chap. 1.5.4 and 1.6 for additional notes.
Offset Designation of the
SIPROTEC objects
Comments Internal
object no.
5/0 CFC-Incoming annunciation 1
(UsCfcSpI1) OFF
5/1 CFC-Incoming annunciation 1
(UsCfcSpI1) ON
Tagging ON/OFF, released as CFC input –