Siemens SIPROTEC4 7SJ65 - Automatic Recloser Status; Time Overcurrent Protection

Siemens SIPROTEC4 7SJ65
66 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Standard mapping 2-2
7SJ61...7SJ63, 7SJ65, 6MD63 PROFIBUS-DP – Bus mapping
C53000-L1840-B006-02
3-6
Offset Designation of the
SIPROTEC objects
Comments Internal
object no.
5/4 Alarm Sum Event 1 = Alarm summary event ON 160
5/5 Relay PICKUP 1 = Relay PICKUP (summary alarm) 501
5/6 Relay TRIP 1 = Relay GENERAL TRIP command
(summary alarm)
511
5/7 <reserved>
3.2.1.6 Automatic recloser status
Offset Designation of the
SIPROTEC objects
Comments Internal
object no.
6/0 >CB Ready 1 = Binary input “circuit breaker ready“ is active 2730
6/1 79 OFF 1 = AR is switched OFF 2781
6/2 79 ON 1 = AR is switched ON 2782
6/3 79 Close 1 = AR close command 2851
6/4 79 Successful 1 = AR successfully completed 2862
6/5 79 Lockout 1 = AR definitive TRIP 2863
6/6 TRIP Gnd Fault 1 = AR TRIP ground fault 2869
6/7 TRIP Ph Fault 1 = AR TRIP phase fault 2870
3.2.1.7 Time overcurrent protection
Offset Designation of the
SIPROTEC objects
Comments Internal
object no.
7/0 50/51 PH OFF 1 = Time overcurrent phase is OFF 1751
7/1 50N/51N OFF 1 = Time overcurrent ground is OFF 1756
7/2 50(N)/51(N) PU 1 = Time overcurrent PICKUP 1761
7/3 50/51 Ph A PU 1 = Time overcurrent phase A picked up 1762
7/4 50/51 Ph B PU 1 = Time overcurrent phase B picked up 1763
7/5 50/51 Ph C PU 1 = Time overcurrent phase C picked up 1764
7/6 50/51N GND PU 1 = Time overcurrent ground picked up 1765
7/7 50(N)/51(N)TRIP 1 = Time overcurrent TRIP 1791
8/0 50-2 TRIP 1 = 50-2 TRIP 1805
8/1 50-1 TRIP 1 = 50-1 TRIP 1815
8/2 51 picked up 1 = 51 picked up 1820
8/3 51 TRIP 1 = 51 TRIP 1825
8/4 50N-2 TRIP 1 = 50N-2 TRIP 1833
8/5 50N-1 TimeOut 1 = 50N-1 TimeOut 1835
8/6 50N-1 TRIP 1 = 50N-1 TRIP 1836
8/7 51N TRIP 1 = 51N TRIP 1839