4.2.2 Measured values
Ref. to chap. 1.3.2 for additional notes regarding scaling of measured values.
4.2.2.1 Recorded measured values
Offset Designation of the
SIPROTEC objects
Comments Scaling
(32767 corresponds to ...)
Internal
object no.
10 Ia = Ia 3276.7 A 601
12 Ib = Ib 3276.7 A 602
14 Ic = Ic 3276.7 A 603
16 In = In 3276.7 A 604
18 Va-b = Va-b 32.767 kV 624
20 Vb-c = Vb-c 32.767 kV 625
22 Vc-a = Vc-a 32.767 kV 626
24 VN = VN 32.767 kV 627
26 P = P (active power) 32.767 MW 641
28 Q = Q (reactive power) 32.767 MVAR 642
30 S = S (apparent power) 32.767 MVAR 645
32 Freq = Frequency 327.67 Hz 644
34 PF = Power Factor 3.2767 901
36 I1 = I1 (positive sequence) 3276.7 A 605
38 I2 = I2 (negative sequence) 3276.7 A 606
40 V1 = V1 (positive sequence) 32.767 kV 629
42 V2 = V2 (negative sequence) 32.767 kV 630
44 Td1= Transducer 1 32.767 mA 996
46 Td2= Transducer 2 32.767 mA 997
4.2.2.2 Measured values – mean values
Offset Designation of the
SIPROTEC objects
Comments Scaling
(32767 corresponds to ...)
Internal
object no.
48 I1 dmd = I1 (positive sequence) demand 3276.7 A 833
50 P dmd = Active power demand 32.767 MW 834