EasyManua.ls Logo

Siemens SIPROTEC4 7SJ65 - Standard mapping 2-4; Message in output direction

Siemens SIPROTEC4 7SJ65
66 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7SJ61...7SJ63, 7SJ65, 6MD63 PROFIBUS-DP – Bus mapping
C53000-L1840-B006-02
5-11
5 Standard mapping 2-4
Standard mapping 2-4
5
5.1 Message in output direction
5.1.1 Double commands (with checkback indication)
Offset Designation of the
SIPROTEC objects
Comments Internal
object no.
0/0 Q0 ON/OFF
OFF
0/1 Q0 ON/OFF
ON
Impulse output,
3 relays (2-pole ON, 1-pole OFF)
0/2 Q1 ON/OFF
OFF
0/3 Q1 ON/OFF
ON
Impulse output,
2 relays, 1-pole
0/4 Q8 ON/OFF
OFF
0/5 Q8 ON/OFF
ON
Impulse output,
2 relays, 1-pole
5.1.2 Single commands (without checkback indication)
Ref. to chap. 1.5.1 and 1.6 for additional notes.
Offset Designation of the
SIPROTEC objects
Comments Internal
object no.
0/6 Output channel E1 (UsrSC5)
OFF
0/7 Output channel E1 (UsrSC5)
ON
Impulse output,
1 relay, 1-pole
5.1.3 Internal commands
Ref. to chap. 1.5.3 for additional notes regarding "Changing the setting group".
Offset Designation of the
SIPROTEC objects
Comments Internal
object no.
1/0 Setting group A
1/1 Setting group A Activation of setting group A
53
1/2 Setting group B
1/3 Setting group B Activation of setting group B
54

Table of Contents