Configuration
6.11 Contactors in safety applications
SIRIUS - SIRIUS 3RT Contactors/Contactor assemblies
130 Manual, 09/2017, A5E03656507120A/RS-AE/006
EMERGENCY STOP shutdown up to SILCL 2 or PL c / Cat. 2
Description
EMERGENCY STOP shutdown
"Detecting" subsystem up to SILCL 2 as per IEC 62061 and PL c / Cat. 2 as per
EN ISO 13849-1
EMERGENCY STOP command device according to ISO 13850
Two-channel sensor interfacing
Cross-circuit monitoring of the sensor wiring
Monitored start
Shutdown via contactor
Stop category 0
"Reacting" subsystem up to SILCL 2 as per IEC 62061 and PL c / Cat. 2 as per
EN ISO 13849-1
Single-channel actuator interfacing
Application
Detection: EMERGENCY STOP
Evaluation: 3SK1 safety relay
Reaction: 3RT1 contactor with fail-safe control input