Configuration
6.11 Contactors in safety applications
SIRIUS - SIRIUS 3RT Contactors/Contactor assemblies
Manual, 09/2017, A5E03656507120A/RS-AE/006
135
EMERGENCY STOP shutdown up to SILCL 3 or PL e / Cat. 4 via an F-DQ
Description
EMERGENCY STOP shutdown
"Detecting" subsystem up to SILCL 3 as per IEC 62061 and PL e / Cat. 4 as per
EN ISO 13849-1
EMERGENCY STOP command device according to ISO 13850
Two-channel sensor interfacing
Discrepancy evaluation between the sensor channels
Cross-circuit monitoring of the sensor wiring
Monitored start
Shutdown of two contactors via a safety-related output
Stop category 0
"Reacting" subsystem up to SILCL 3 as per IEC 62061 and PL e / Cat. 4 as per
EN ISO 13849-1
Redundant actuators
Use of one safety-related output on the fail-safe controller when actuator cables are laid
unprotected in the field.