Loading...
Configuration
6.11 Contactors in safety applications
SIRIUS - SIRIUS 3RT Contactors/Contactor assemblies
138 Manual, 09/2017, A5E03656507120A/RS-AE/006
EMERGENCY STOP shutdown up to SILCL 2 or PL c / Cat. 2
Description
EMERGENCY STOP shutdown
"Detecting" subsystem up to SILCL 2 as per IEC 62061 and PL c / Cat. 2 as per
EN ISO 13849-1
EMERGENCY STOP command device according to ISO 13850
Single-channel sensor interfacing
Monitored start
Shutdown via contactor
Stop category 0
"Reacting" subsystem up to SILCL 2 as per IEC 62061 and PL c / Cat. 2 as per
EN ISO 13849-1
Single-channel actuator interfacing
Application
Detection: EMERGENCY STOP
Evaluation: SIMATIC S7-1500 automation system (fail-safe CPU for medium to large
applications CPU 1515F-2 PN, digital input module F-DI, digital output module F-DQ, digital
input module DI)
Reaction: 3RT1 contactor with fail-safe control input