EasyManua.ls Logo

Siemens SIRIUS 3RT - Mounting Size S0

Siemens SIRIUS 3RT
552 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Accessories
9.28 Assembly kit for contactor assemblies for star-delta (wye-delta) start (sizes S00 to S3)
SIRIUS - SIRIUS 3RT Contactors/Contactor assemblies
Manual, 09/2017, A5E03656507120A/RS-AE/006
399
9.28.3
Mounting size S0
The contactor assemblies for star-delta (wye-delta) start can be built from contactors with
screw connections or spring-loaded connections:
Line contactor (Q11): Left
Delta contactor (Q13): Center
Star contactor (Q12): Right
This arrangement applies for all installation instructions described in this chapter.
The illustration below shows example procedures for assembling the contactor assembly for
star-delta (wye-delta) start in size S0 with screw-type connection. Instructions 1 to 6 show
how to assemble the contactors using the components supplied in the assembly kit.
Assembling the contactor assembly for star-delta (wye-delta) start with screw-type connection - size
S0
Electrical interlocking is available only if no 3RA28 is used.
Insert the connecting clips into the openings on contactor Q13.
Secure the mechanical interlock on the left-hand side of contactor Q12.
Connect contactors Q11 and Q13 together.
Insert the connecting clips into the openings on contactor Q12.
Connect contactors Q11/Q13 and Q12 together.

Table of Contents

Related product manuals