EasyManua.ls Logo

Siemens SIRIUS 3RU - Page 45

Siemens SIRIUS 3RU
206 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Product description
3.8 3RB31 solid-state overload relays
SIRIUS 3RU thermal overload relays / SIRIUS 3RB electronic overload relays
Manual, 09/2016, A5E03656507420A/RS-AB/003
45
3RB3143 electronic overload relays, size S3, 70 mm width
Front view
Description
3RB3143 overload relay equipment
Position digits
Connection for contactor mounting:
In terms of their electrical and mechanical
features and their design, these pins are
perfectly compatible with the
3RT2 contactors for the direct mounting of
overload relays. Stand-alone assembly is
also an option (in some cases in conjunction
with a stand-alone assembly module).
Switch position indicator and TEST function
for wiring:
Indicates a trip and facilitates testing of the
wiring.
RESET button
A device set to manual RESET can be reset
locally by pressing the RESET button. In
addition, an electronic remote RESET is
integrated into the 3RB31.
Tripping class setting / internal ground-fault
detection (3RB31 only):
The rotary switch is used to set the required
tripping class dependent upon the starting
conditions and activate internal ground-fault
detection.
Electronics test (device test):
Enables a test of all major device
components and functions.
Control circuit terminal (removable):
A screw-type or spring-loaded system can
be used to connect the control circuit
terminal.
Main circuit terminal:
The main circuit can be connected using
either the screw-type connection system or
through-hole technology with straight-
through transformer. Ring terminal lug
connection or busbar connection after
removal of the box terminal block is
optionally possible.
Selector switch for manual/automatic
RESET and RESET button:
The slide switch is used to choose between
manual and automatic RESET.
Data Matrix code
Motor current setting:
The large rotary button provides an easy
means of setting the device to the rated
motor current.
Label

Table of Contents

Related product manuals