Configuration
6.5 Safety instructions for use in hazardous areas (3RB)
SIRIUS 3RU thermal overload relays / SIRIUS 3RB electronic overload relays
Manual, 09/2016, A5E03656507420A/RS-AB/003
71
Resetting the electronic overload relay is described in the Chapter "RESET after release
(Page 117)".
Testing in accordance with EN 60079-17 can be combined with the user test. Operation of
the device must be discontinued if the test result is negative.
Qualified personnel required
The test must be performed by a qualified person familiar with the specified standards.
● The three phase currents that flow through the 3RB electronic overload relay must be
largely symmetrical.
● The phase currents must amount to ≥ 80 % of the set current I
e
.
● The currents must flow for at least the time t
1
before testing.
● The phase currents must be at least as high as the value of the bottom current setting
marker.
Required loading with
the rated current prior to
pressing the TEST button
1