EasyManua.ls Logo

Siemens SIRIUS 3RW44 - Order Number Classification for SIRIUS 3 RW44 Soft Starters

Siemens SIRIUS 3RW44
255 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Configuration Instructions
SIRIUS 3RW44 System Manual
2-8 GWA 4NEB 535 2195-02 DS 04
2.6 Order Number Classification for SIRIUS 3RW44 Soft Starters
Order number classification using the 3RW44 22-6BC44 as an example
*Gray fields cannot be configured
3RW4 422- 6 B C44
I II III IV V VI VII VIII
I Designation of the basic unit:
Semiconductor AC motor control device (soft starter)
II Device version:
4 High End soft starter
III Operating efficiency rating P
e
(at U
e
400 V)
Rated operating current I
e
(for utilization category AC-53a) (at TU 40 °C)
P
e
I
e
P
e
I
e
22 - 15 kW 29 A 45 - 160 kW 313 A
23 - 18.5 kW 36 A 46 - 200 kW 356 A
24 - 22 kW 47 A 47 - 250 kW 432 A
25 - 30 kW 57 A 53 - 315 kW 551 A
26 - 37 kW 77 A 54 - 355 kW 615 A
27 - 45 kW 93 A 55 - 400 kW 693 A
34 - 55 kW 113 A 56 - 450 kW 780 A
35 - 75 kW 134 A 57 - 500 kW 880 A
36 - 90 kW 162 A 58 - 560 kW 970 A
43 - 110 kW 203 A 65 - 630 kW 1076 A
44 - 132 kW 250 A 66 - 710 kW 1214 A
IV Type of connection
1 - Standard screw connection (main/auxiliary lead connection)
(for devices
3RW44 27)
2 - Main lead: Conductor-rail bond / auxiliary lead: Spring-type terminal
(for devices > 3RW44 27)
3 - Main lead: Screw connection / auxiliary lead: Spring-type terminal
(for devices
3RW44 27)
6 - Main lead: Conductor-rail bond / auxiliary lead: Terminal screw (for
devices > 3RW44 27)
V Special function:
B - With bypass:
VI Number of controlled phases:
C - All 3 phases controlled
VII Rated control supply voltage U
s
:
3-115V AC
4-230V AC
VIII Rated operating voltage U
e
:
4 - 200 to 460 V
5 - 400 to 600 V
6 - 400 to 690 V

Table of Contents