Commissioning
SIRIUS 3RW44 System Manual
5-14 GWA 4NEB 535 2195-02 DS 04
"Voltage ramp" starting mode
Figure 5-8:"Voltage ramp" starting mode
4_1_Menü_Startart_Spannungsrampe.wmf
Voltage in %
U
Motor
100 %
Breakaway voltage
Start voltage
Breakaway time
starting time
Maximum starting time
100 % Voltage
at the motor
Time (t)
s
change
ESC
Starting mode
1
select
ESC
Starting
2
OK
settings
Voltage ramp
OK
change
ESC
Start voltage
2
40.0 %
OK
change
ESC
Starting time
5
20 s
OK
change
ESC
Maximum start-
6
deactivated
OK
ing time
change
ESC
Breakaway
8
80 %
OK
voltage
change
ESC
Breakaway time
9
0 ms
OK
Adjustable
from ... to
20 ... 100 %
0 ... 360 s
1 ... 1,000 s
40 ... 100 %
0 ... 2,000 ms
select
ESC
Motor 1
1
select
ESC
Parameter
1
set 1
select
ESC
Settings
3
OK
Display mea-
SIEMENS
Menu
3RW44
1
ESC
ESC OK
OK
select
Status display
select
2
ESC OK
OK
OK
OK
OK
value