Parameter assignment
6.7 Parameterize output 13, 14 (output signal ON or RUN)
SIRIUS 3RW52 Soft Starter
Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005
107
Procedure
1. Start programming by pressing the MODE key longer than 2 seconds until the
STATE / OVERLOAD LED flickers green.
Press and hold the MODE key.
2. Also press the RESET / TEST key longer than 2 seconds until the
LED STATE / OVERLOAD illuminates red.
The set state of ON / RUN relay output is displayed on the SOFT TORQUE LED:
SOFT TORQUE LED
Signal set at output 13, 14
Flashes green
ON (factory setting)
Flickers green
RUN
3. Release the MODE and RESET / TEST keys.
4. Switch the mode by pressing the MODE key briefly. The SOFT TORQUE LED switches
between flickering green and flashing green.
You can switch between the modes at the output as often as you want.
Note
If you do not press a key in the programming mode for longer than 10
seconds, the
3RW
52 soft starter automatically terminates the programming mode.
5. Terminate programming mode by pressing the RESET / TEST key for longer than
1 second until the STATE / OVERLOAD LED no longer shines red.
Further parameterization options
3RW5 HMI High Feature (accessory)
Menu: "Parameters > Soft Starter > ON / RUN relay output"
Procedure in chapter Parameterize the response to bus errors and output 13, 14
(ON / RUN) (Page 108)