Setting options
3RW5 HMI High Feature
Menu: "Parameters > Soft Starter > Outputs"
Access protection to the 3RW5 HMI High Feature is not active or has been reset.
With SIRIUS Soft Starter ES (TIA Portal) via the local interface on the 3RW5 HMI High Feature
Brief overview: Window "Project Navigation" with current project under created Soft Starter >
"Parameters" > Window "Work area" > "Soft Starter > Outputs > Soft Starter"
With a 󹪝eldbus via a 3RW5 communication module:
With SIRIUS Soft Starter ES (TIA Portal) Premium / Professional (only via a 3RW5 PROFINET
or PROFIBUS communication module)
Brief overview: See SIRIUS Soft Starter ES (TIA Portal) via the local interface on the
3RW5 HMI High Feature
Con󹪝guration software of the control system (e.g. STEP 7 with corresponding HSP)
User program
You can 󹪝nd additional information on the parameters that can be set via the 󹪝eldbus in the
manual of the respective 3RW5 communication module.
Parameter - Delay
Parameters Description
ON delay time The switching of the output is delayed by this time.
Factory setting: 0 s
Setting range: 0 ... 6 500 s
In steps of: 0.1 s
OFF delay time
Parameter - Output action
Output action Description Factory setting
DQ1 DQ2 DQ3
1)
DQ4
2)
No action - - x - x
Activation by external control sources
Control source PIQ-DQ-1.0 output 1 The control command "Output 1" is assigned to the
corresponding digital output.
Refer to chapter Control via 3RW5 HMI High Fea‐
ture (Page 232).
- - - -
Control source PIQ-DQ-1.1 output 2 The control command "Output 2" is assigned to the
corresponding digital output.
Refer to chapter Control via 3RW5 HMI High Fea‐
ture (Page 232).
- - - -
Control source PIQ-DQ-2.0 output 3
3)
The control command "Output 3" is assigned to the
corresponding digital output.
Refer to chapter Control via 3RW5 HMI High Fea‐
ture (Page 232).
- - - -
Control source input 1 Digital output is activated by "Digital input 1". - - - -
Functions
8.13 Outputs
SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters
200 Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006