EasyManua.ls Logo

Siemens SIRIUS 3RW55 - A.2.4 Connecting the Temperature Sensor

Siemens SIRIUS 3RW55
238 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Example circuits
A.2 Control circuit connection
SIRIUS 3RW55 soft starter
210 Manual, 08/2018, A5E35630887002A/RS-AB/002
A.2.4
Connecting the temperature sensor
Requirements
Motor with temperature switch (e.g. Thermoclick) or thermistor (e.g. PTC type A)
Parameterization required
Procedure
1. Connect the temperature sensor:
Temperature switch at terminals T1-T2 Thermistor at terminals T1-T2
2. Parameterize the temperature sensor.
You will find more information on parameterizing the temperature sensor in Chapter
Thermistor motor protection with temperature sensor (Page 112).
Result
The 3RW55 soft starter monitors the motor for excessive temperature. If the temperature is
exceeded, a warning is generated or the motor is switched off depending upon the
parameterization. Restarting takes place after a reset.