AS-Interface 3SU14
11.10 Configuring the AS-Interface
SIRIUS ACT 3SU1 pushbuttons and signaling devices
System Manual, 08/2018, A5E03457306020A/RS-AK/010
289
Offlline addressing with the addressing unit
Procedure
1. Connect the module to the addressing unit 3RK1904-2AB02.
2. Assign an address to the module:
Switch the selector switch to
ADDR.
Press . The address of the connected module is read and displayed.
Select the address with
.
Transfer the address to the module with
.
3. Remove the addressing cable.
11.10.2
Addressing the AS-Interface modules for front plate mounting
To address the AS-Interface modules for front plate mounting, connect the
3RK1904-2AB02 AS-Interface addressing unit.