Safety Integrated Basic Functions
10.11 Acceptance test and acceptance report
Drive functions
726 Function Manual, 11/2017, 6SL3097-4AB00-0BP5
Acceptance test for Safe Stop 1, time controlled (SS1)
The acceptance test must be individually performed for each configured control.
The control can be realized via TM54F, onboard terminals (CU310-2) or via PROFIsafe.
1.
• Drive in the "Ready" state (p0010 = 0)
• STO function enabled (onboard terminals/PROFIsafe/TM54F)
• SS1 function enabled (p9652 > 0)
• Only for "SS1 with external stop"
p9653 = 1
• No safety faults and alarms (r0945[0...7], r2122[0...7]); see note "non-critical alarms" at
the beginning of Section "Acceptance test".
• r9772.22 = 0 (SS1 deselection via terminals – DI CU / EP terminal Motor Module); only
relevant for SS1 via terminal
• r9772.23 = 0 (SS1 deselection via PROFIsafe); only relevant for SS1 via PROFIsafe
• r9773.0 = r9773.1 = 0 (STO deselected and inactive – drive)
• r9773.5 = r9773.6 = 0 (SS1 deselected and inactive – drive)
• r9774.0 = r9774.1 = 0 (STO deselected and inactive – group); only relevant for grouping
• r9774.5 = r9774.6 = 0 (SS1 deselected and inactive – group); only relevant for grouping
2. Run the drive
Check whether the correct drive is operational
Select SS1 when you issue the traversing command and check the following:
• Drive brakes along the OFF3 ramp (p1135) (not in the case of SS1 with external stop)
Before the expiry of the SS1 delay time (p9652), the following applies:
• r9772.22 = 1 (SS1 selection via terminals – DI CU / EP terminal Motor Module); only rele-
vant for SS1 via terminal
• r9772.23 = 1 (SS1 selection via PROFIsafe); only relevant for SS1 via PROFIsafe
• r9773.0 = r9773.1 = 0 (STO deselected and inactive – drive)
• r9773.5 = r9773.6 = 1 (SS1 selected and active – drive)
• r9774.0 = r9774.1 = 0 (STO deselected and inactive - group); only relevant for grouping
• r9774.5 = r9774.6 = 1 (SS1 selected and active - group); only relevant for grouping
STO is initiated after expiry of the SS1 delay time (p9652).
• No Safety faults and alarms (r0945[0...7], r2122[0...7])
• r9773.0 = r9773.1 = 1 (STO selected and active – drive)
• r9773.5 = r9773.6 = 1 (SS1 selected and active – drive)
• r9774.0 = r9774.1 = 1 (STO selected and active – group); only relevant for grouping