Communication
11.4 Communication via MODBUS TCP
Drive functions
Function Manual, 11/2017, 6SL3097-4AB00-0BP5
871
Process data monitoring time (setpoint timeout)
The "Setpoint timeout" only applies for access to process data (40100 ... 40109, 40110 ...
40119). The "Setpoint timeout" is not generated for parameter data (4030040522).
Fieldbus interface:
In parameter p2040 you define the time for cyclic data exchange for process data.
Setting range 0 - 2000 s.
The time depends on the amount of data to be transferred and the control.
"Setpoint timeout" (F01910) is issued by the Modbus if p2040 is set to a value > 0 ms and no
process data is requested within this time period.
COMM BOARD:
In parameter p8840 you define the time for cyclic process data exchange.
Setting range 0 - 2000 s.
The time depends on the amount of data to be transferred and the control.
"Setpoint timeout" (F08501) is issued by the Modbus if p8840 is set to a value > 0 ms and no
process data is requested within this time period.
11.4.8
Messages and parameters
Faults and alarms (see SINAMICS S120/S150 List Manual)
F01910
Fieldbus: Setpoint timeout
A01925 (F)
Modbus TCP connection interrupted
F08501 (N, A)
PN/COMM BOARD: Setpoint timeout
A08526 (F)
PN/COMM BOARD: No cyclic connection
A08555
Modbus TCP commissioning fault

Table of Contents

Other manuals for Siemens SIROTEC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIROTEC and is the answer not in the manual?

Siemens SIROTEC Specifications

General IconGeneral
BrandSiemens
ModelSIROTEC
CategoryDC Drives
LanguageEnglish

Related product manuals