Description, device design, dimension drawing
2.5 Change-over switch
SITOP modular 1ph/2ph
Manual, 04.2018, C98130-A7548-A1-4-7629
15
Selector switch for the input voltage range for 6EP1333-3BA10 (24 V/5 A) and 6EP1334-
3BA10 (24 V/10 A)
Figure 2-8 Voltage selector switch (example, 6EP1334-3BA10)
The selector switch as delivered is in the 230 V position. It must be moved to the appropriate
position for operation in the 120 V range. The selector switch can only be actuated in the de-
energized state.
To switch the input voltage range for 6EP1336-3BA00 (24 V/20 A) and 6EP1337-3BA00
(24 V/40 A) to 120 V, a wire jumper must be connected to the input terminal, Jump 120 V
AC. This must be dimensioned as for the power supply cable with regard to cross-section
and insulation. The length must not exceed 100 mm.
Figure 2-9 Wire jumper (example, 6EP1437-3BA00)