Technical data
6.4 Closed-loop control
SITOP modular 1ph/2ph
48 Manual, 04.2018, C98130-A7548-A1-4-7629
6EP1334-3BA10
(24 V/10 A)
6EP1336-3BA00
(24 V/20 A)
6EP1337-3BA00
(24 V/40 A)
Dyn. line regulation
0.1 % 0.1 % 1 % 1 %
Dyn. load regulation
(I
out
: 50/100/50 %), U
out
±
3 % 3 % 2 % 2 %
Load step regulation time
2 ms 2 ms 2 ms 2 ms
Load step regulation time
2 ms 2 ms 2 ms 2 ms
Protection and monitoring
6EP1334-3BA10
(24 V/10 A)
6EP1336-3BA00
(24 V/20 A)
6EP1337-3BA00
(24 V/40 A)
Output overvoltage pro-
< 35 V < 35 V < 35 V < 35 V
Property of the output:
Yes
Optional constant current characteristic curve or latching shutdown
Continuous short-circuit
5.5 A 12 A 23 A 46 A
Overload / short-circuit
Yellow LED for "overload", red LED for "latching shutdown"
6EP1333-3BA10 (24 V/5 A)
6EP1334-3BA10 (24 V/10 A)
6EP1336-3BA00 (24 V/20 A)
6EP1337-3BA00 (24 V/40 A)
Mean Time Between Fail-
SN29500: > 500000 h (typ. 700000 h) at 40 °C, rated load, 24 hour operation