Technical data
6.2 Output
SITOP modular 1ph/2ph
40 Manual, 04.2018, C98130-A7548-A1-4-7629
6EP1334-3BA10
(24 V/10 A)
6EP1336-3BA00
(24 V/20 A)
6EP1337-3BA00
(24 V/40 A)
Short-time overload current for
a short circuit in operation, typ.
15 A 30 A 60 A 120 A
Duration of the overload capa-
bility for an overcurrent condi-
tion caused by a short circuit in
operation.
• Remark
25 ms
Every 1 min
25 ms
Every 1 min
25 ms
Every 1 min
25 ms
Every 1 min
Can be connected in parallel to
increase the power rating
• Remark
Yes
Switchable characteristic curve with switch A (see
Status displays
Number of devices that can be
connected in parallel to in-
crease the power rating, quan-
2
Output characteristic See Figure 6-3
6EP1333-3BA10
single operation
output characteristic
See Figure 6-4
6EP1334-3BA10
single operation
output characteristic
See Figure 6-5
6EP1336-3BA00
single operation
output characteristic
See Figure 6-6
6EP1337-3BA00
single operation
output characteristic
Figure 6-2 Startup delay/voltage rise