EasyManua.ls Logo

Siemens SITOP PSU8600 - Page 27

Siemens SITOP PSU8600
94 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Blocks of the library
5.2 Explanation of SIMATIC STEP 7 blocks
SITOP PSU8600 Firmware V1.3: Faceplates and Communication Blocks V2.3 for SIMATIC STEP 7 V5.5
Function Manual, 11.2017, A5E37764016-06-76
27
Input parameters
Table 5- 11
Parameter
Data type
Description
Execute
Bool On the rising edge (0 > 1), data at the
inputs of the block is written to the
PSU.
HW_Ident_Head
WORD Start address of the entire main mod-
ule.
Cyclic_IO_OUT_Head_addr
WORD Output address of main module I/O
data submodule.
Device_In_Parameters
UDT_General_PSU_IN_V2
UDT for device input parameters.
Structure of UDT_General_PSU_IN_V2 data type
Table 5- 12
Parameter
Data type
Description
Priority_Buffered_Ch1
BYTE During a network failure, output 1 of the main module
can be supplied with priority.
(0 = no, 1 = yes)
Startup_Mode
BYTE Switch-on behavior.
0 = no switch-on delay
1 = switch-on delay of 25 ms
2 = switch-on delay of 100 ms
3 = load-optimized switch-on delay
4 = variable switch-on delay
Ithreshold
BYTE
Pre-alarming threshold (0 to 100 %) for alarming.
Parallel12
BYTE Outputs 1 and 2 are switched parallel. Output 2 fol-
lows output 1. (Values for output 2 are ignored.)
Parallel34
BYTE Outputs 3 and 4 are switched parallel. Output 4 fol-
lows output 3. (Values for output 4 are ignored.)
Reset
BYTE Outputs switched off due to overload are switched on
again, if they are ready for it.
0 = normal state (no actions taken)
1 = switched on again (attention, the value must be
reset to 0 after switching on.)
SysOverloadAlarmThr
WORD
System overload alarm threshold time (0 to 60000 ms)
MainPowerOutageAlarmThr
WORD Main power outage alarm threshold time
(0 to 1000 ms)

Other manuals for Siemens SITOP PSU8600

Related product manuals