Blocks of the library
5.2 Explanation of SIMATIC STEP 7 blocks
SITOP PSU8600 Firmware V1.3: Faceplates and Communication Blocks V2.3 for SIMATIC STEP 7 V5.5
32 Function Manual, 11.2017, A5E37764016-06-76
Table 5- 17
Bool On the rising edge (0 > 1), data at the
inputs of the block is written to
WORD Start address of the entire main module
Cyclic input address of the output
Cyclic output address of the output
Note
Output_Number parameter
Irrespective of the type of the main module connected, output numbering of CNX8600 4X is
5 to 20. For main modules with 4 outputs, for example: PSU8600 24 V/40
A/4x10 A:
1 to 4 + CNX8600 24 V/4x10 A: 5 to 20 and for main modules with 1 output, for example:
PSU8600 24 V/40 A:1 + CNX8600 24 V/4x10 A: 5 to 20.
The output numbering of CNX8600 8X is 5 to 36. For main modules with 4 outputs, for
example: PSU8600 24 V/
40 A/4x10 A: 1 to 4 + CNX8600 24V/8x2.5 A: 5 to 36 and for main
modules with 1 output, for example: PSU8600 24 V/40 A:1 + CNX8600 24 V/8x2.5 A: 5 to 36
Structure of UDT_Output_PSU_IN_V2 data type
Table 5- 18
INT Target voltage of the output in millivolt. (10 mV
INT Current limit of the output in milliampere. (10 mA
Pre-alarming threshold (0 to 100%) for alarming.
Switching the output on/off. (0 = off; 1 = on)
Resetting the output (0 = no reset; 1=reset)
BYTE Operating mode of the output. (0 = electronic
switch-off and 1 = constant current)
Switch-on delay of the output. (0 to 60000 ms)