Blocks of the library
5.2 Explanation of SIMATIC STEP 7 blocks
SITOP PSU8600 Firmware V1.3: Faceplates and Communication Blocks V2.3 for SIMATIC STEP 7 V5.5
Function Manual, 11.2017, A5E37764016-06-76
33
Input/output parameters
Table 5- 19
Parameter
Data type
Description
Data
UDT_PSU8600_Data_V2 Data block for global data exchange. DB must
follow the UDT structure.
Output parameters
Table 5- 20
Parameter
Data type
Description
Output_Out_Parameter
UDT_Output_OUT_V2 UDT for output values
Busy
BOOL
Block operation active
Done
BOOL
Block operation completed
Error
WORD Errors at last block operation. Refer the section
Description of Error parameter below.
Structure of UDT_Output_OUT_V2 data type
Table 5- 21
Parameter
Data type
Description
Imax
INT Maximal current of the output in milliampere.
(Smallest resolution 10 mA)
Output_voltage
INT Current output voltage in millivolt. (10 mV reso-
lution)
Output_current
INT Current output current in milliampere. (10 mA
resolution)
Operating_state
BYTE Current operating state.
0 = Output manually switched off
1 = Output switched off (PROFINET/IE)
2 = Output switched off (prioritizing output 1)
3 = Output switched off (overload)
4 = Output ready for reset (reset)
5 = Output switched off (error)
6 = Output switched off (startup)
7 = Output switched on (normal operation)
8 = Output in overload mode
9 = Output current-limited (with derating)
10 = Output in overload mode (with derating)
11 = Output current-limited (with derating)
Parallel_mode
BYTE Parallel mode active (0 = normal; 1 = output
switched parallel) → valid only for main module
with 4 outputs.