Blocks of the library
5.2 Explanation of SIMATIC STEP 7 blocks
SITOP PSU8600 Firmware V1.3: Faceplates and Communication Blocks V2.3 for SIMATIC STEP 7 V5.5
Function Manual, 11.2017, A5E37764016-06-76
33
Table 5- 19
UDT_PSU8600_Data_V2 Data block for global data exchange. DB must
follow the UDT structure.
Table 5- 20
UDT_Output_OUT_V2 UDT for output values
Block operation completed
WORD Errors at last block operation. Refer the section
Description of Error parameter below.
Structure of UDT_Output_OUT_V2 data type
Table 5- 21
INT Maximal current of the output in milliampere.
(Smallest resolution 10 mA)
INT Current output voltage in millivolt. (10 mV reso-
INT Current output current in milliampere. (10 mA
BYTE Current operating state.
0 = Output manually switched off
1 = Output switched off (PROFINET/IE)
2 = Output switched off (prioritizing output 1)
3 = Output switched off (overload)
4 = Output ready for reset (reset)
5 = Output switched off (error)
6 = Output switched off (startup)
7 = Output switched on (normal operation)
8 = Output in overload mode
9 = Output current-limited (with derating)
10 = Output in overload mode (with derating)
11 = Output current-limited (with derating)
BYTE Parallel mode active (0 = normal; 1 = output
switched parallel) → valid only for main module