EasyManua.ls Logo

Siemens SITOP PSU8600 - Page 40

Siemens SITOP PSU8600
94 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Blocks of the library
5.2 Explanation of SIMATIC STEP 7 blocks
SITOP PSU8600 Firmware V1.3: Faceplates and Communication Blocks V2.3 for SIMATIC STEP 7 V5.5
40 Function Manual, 11.2017, A5E37764016-06-76
Input parameters
Table 5- 29
Parameter
Data type
Description
Execute
BOOL On the rising edge (0 > 1), data at the
inputs of the block is written to the
PSU.
HW_Ident_Head
WORD Start address of the entire main mod-
ule.
Cyclic_IO_OUT_Head_addr
WORD Output address of main module IO
data submodule.
Device_In_Parameters
UDT_General_PSU_S_IN_V2
UDT for device input parameters
Structure of UDT_General_PSU_S_IN_V2 data type
Table 5- 30
Parameter
Data type
Description
Priority_Buffered_Ch1
BYTE During a network failure, output 1 of the main
module can be supplied with priority.
(0 = no, 1= yes)
Startup_Mode
BYTE Switch-on behavior.
0 = no switch-on delay
1 = switch-on delay 25 ms
2 = switch-on delay 100 ms
3 = load optimized switch-on delay
4 = variable switch-on delay
Ithreshold
BYTE
Pre-alarming threshold (0 to 100 %) for alarming.
Reset
BYTE Outputs switched off due to overload and are
switched back on if they are ready for it.
0 = normal state (no actions taken)
1 = switched back on (attention, the value must
be reset to 0 after switching on.)
Soft_Output_Char
BYTE Soft output characteristics (False = 0, True = any
non-zero value)
Padding
BYTE
Unused
SysOverloadAlarmThr
WORD System overload alarm threshold time
(0 to 60000 ms)
MainPowerOutageAlarmThr
WORD Main power outage alarm threshold time
(0 to 1000 ms)

Other manuals for Siemens SITOP PSU8600

Related product manuals